CDC Series Chain drives
CDC-0252-0350-1-ACB-BB
-
Can be used for openings for smoke exhaust, D+H Euro SHEV in accordance with EN 12101‑2 and for daily ventilation
-
With BSY+ motor and synchronised electronics controlled via microprocessor
-
Low running noises thanks to the innovative acoustic decoupling of the drive components
-
Special side-hung vent bracket sets with compression springs for installation (included in scope of supply)
-
Available in all RAL colours
-
Can be used for virtually all window openings with an opening angle of up to 90°
-
Integrated ACB (Advanced Communication Bus) bus interface with Modbus RTU protocol
-
The drive is integrated directly via open bus communication through the ACB (Advanced Communication Bus), e.g. in a building management system
Approvals / Certificates
Designs and technical data
| CDC-1-ACB | CDC-0252-0350-1-ACB-BB | CDC-0252-0350-1-ACB-BB-M1-R | CDC-0252-0350-1-ACB-BB-M2-R | CDC-0252-0350-1-ACB-BB-S1-L | |
|---|---|---|---|---|---|
| Supply | Configuration dependent | 24 V DC / ±15 % / 0.6 A | 24 V DC / ±15 % / 0.6 A | 24 V DC / ±15 % / 0.6 A | |
| Duty cycle | Variable designs possible | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) |
| Configuration | - |
Main 1 |
Main 2 |
Sub 1 |
|
| Force of pressure | 250 N | 250 N | 250 N | 250 N | |
| Tensile force | 250 N | 250 N | 250 N | 250 N | |
| Nominal locking force * |
1500 N |
1500 N |
1500 N |
1500 N |
|
| Service life | 20000 double strokes | 20000 double strokes | 20000 double strokes | 20000 double strokes | |
| Stroke | 350 mm | 350 mm | 350 mm | 350 mm | |
| Max. opening angle |
Ventilation 45° |
Ventilation 45° |
Ventilation 45° |
Ventilation 45° |
|
| Max. permissible force 45° opening |
700 N |
700 N |
700 N |
700 N |
|
|
Show more information
|
|||||
| Request & Compare |
CDC-1-ACB |
CDC-0252-0350-1-ACB-BB
|
CDC-0252-0350-1-ACB-BB-M1-R
|
CDC-0252-0350-1-ACB-BB-M2-R
|
CDC-0252-0350-1-ACB-BB-S1-L
|
| Configure now | |||||
* Depending on the mounting, ** in accordance with VdS 2580